Product Overview
Product Details
Data Download
Related Products
Series YCM8C ambitus externi ruptorum aptae sunt ad retiacula distribuenda cum AC 50Hz vel 60Hz, in voltage insulation 1000V aestimata, intentione 400V et infra aestimata, et currenti 1000A aestimata. In communibus adiunctis, circumitus ruptor adhiberi potest pro infrequentia in lineae potestate et in usu infrequens initium.
Contact Us
General
Series YCM8C ambitus externi ruptorum aptae sunt ad retiacula distribuenda cum AC 50Hz vel 60Hz, in voltage insulation 1000V aestimata, intentione 400V et infra aestimata, et currenti 1000A aestimata. In communibus adiunctis, praevaricator ambitus adhiberi potest ad infrequentem in potestate lineae et rari principium respective motoris.
Standard: IEC60947-2;
Conditiones operating
1. Extrema temperatus range repositionis et vecturae: -10°C ad 85°C;
2. operating range: -10°C ad 75°C;
3. temperatura Reference: 55°C;
4. Conditiones atmosphaerae: Maxima temperies 75 obolum est, et maxima humiditas relativa 95% est;
5. Agros magnetici externi ad institutionem situs non excedere 5 vicibus vires agri magnetici terrae, et productum ab intercursu electromagnetico valido arceri (qualia sunt motores vel inverters summus potentiae). Non sint vapores explosivi vel mordores, nulla detectio pluviis vel nivis, et ambitus siccus et bene ventilatus debet esse;
6. pollutio level: level 3; categoriae institutionis: categoria III.
Technica notitia
Artus current Inm (A) | 250S | 400S | 630S | 800S | 1000S | |
Opus voltage Ue (V) | 400 | |||||
Nulla voltage Rated Ui (V) | AC1000 | |||||
Ratum impetum sustinere voltage Uimp(KV) | 8 | |||||
Numerus polorum (P) | 3 | |||||
Rated current in (A) | 100,125, 140,160; 180,200,225,250 | 250,315,350,400 | 400,500,630 | 630,700,800 | 800,1000 | |
Ultima solveret facultatem Icu (KA) | AC240V | 35 | 50 | 50 | 65 | 65 |
AC415V | 25 | 35 | 35 | 40 | 40 | |
Ics operating facultatem fractionis (KA) | AC240V | 35 | 50 | 50 | 65 | 65 |
AC415V | 25 | 25 | 25 | 40 | 40 | |
Electrical vita (tempora) | 1000 | 1000 | 1000 | 500 | 500 | |
Mechanica vita (tempora) | 7000 | 4000 | 4000 | 2500 | 2500 | |
Operans voltage | AC230V(85%~110%) | |||||
Wiring | Ascende et descende, descende et ascende foras | |||||
Praesidium gradum | IP30 | |||||
Munus solitudo | Ita | |||||
Genus supplantat | Thermomagnetic | |||||
Accessories | Shunt, terror, auxilia | |||||
Testimonium | CE |
Product pluma configuratione
Operatio machinalis machinae electricae operantis in Figura 1 . ostenditur
1. Circuit ruptor status indicationem fenestra
2. Mechanismus cincinno
3. Tripping button
4. Potestas et imperium wiring portuum
5. Manual and automatic switching of cover plates
Electrical control schematic
Altiore et ascendens dimensiones
Specifications | 250/3P | 400/3P | 630/3P | 800/3P | 1000/3P |
L | 165 | 257 | 275.5 | 275.5 | 275.5 |
W | 105 | 140 | 210 | 210 | 210 |
A | 35 | 43.5 | 70 | 70 | 70 |
B | 144 | 230 | 243.5 | 243.5 | 243.5 |
C | 24 | 31 | 45 | 45 | 45 |
D | 21 | 29 | 30 | 30 | 30 |
E | 22.5 | 30 | 24 | 26 | 28 |
F | 118 | 160 | 175 | 175 | 175 |
a | 126 | 194 | 243 | 243 | 243 |
b | 35 | 44 | 70 | 70 | 70 |
Φd | 4×Φ4.5 | 4×Φ7 | 4×Φ8 | 4×Φ8 | 4×Φ8 |
Dimensiones cum protective cover
Magnitudo | 250/3P | 400/3P | 630/3P | 800/3P | 1000/3P |
A | 208 | 278 | 418 | 418 | 418 |
B | 105 | 140 | 238 | 238 | 238 |
C | 67.5 | 103 | 103 | 103 | 103 |