KYN61-40.5 Metalclad AC Inclusum Switchgear
Picture
  • KYN61-40.5 Metalclad AC Inclusum Switchgear
  • KYN61-40.5 Metalclad AC Inclusum Switchgear

KYN61-40.5 Metalclad AC Inclusum Switchgear

1. ONERO praesidio
2. Brevi circuitu praesidio
3. Controlling
4. In residentialibus aedificationibus, non residentialibus aedificiis, industria fons industriae et infrastructuris usus est.
5. Secundum genus emissio instantaneae sic indicatur: genus B (3-5)ln, genus C (5-10)ln, genus D (10-20) ln

Conatct Us

Product Details

Medium Voltage Switchgear
KYN61-40.5 Metalclad AC Clausum Switchgear, Withdrawable Type

KYN61-40.5 Aeris insulata metallica vestita commutabilis mobilis est switchgear umbratica, conventus operans sub conditionibus 50/60Hz trium phase ac 40.5kV AC voltages aestimavit, quod ad generantium transmissionem et distributionem, transformantium substations et industriam ac meam applicatur. aggressus est.Etiam adhiberi potest ad moderandum, protegendum et monitor electricum electricum, et valde utile est ad crebras conditiones operandas.
Standard: IEC62271-200

Electio

1

Conditiones operating
1.Ambient aeris temperies: -15℃~+40℃
2.Altitude: ≤1000m
3.Relativa humiditas : Quotidie average≤95%;Monthly average≤90% 4. Terrae motus 4.intensity:≤magnitudo 8.
5. Applicable in locis sine gas exedunt et fomes.
Nota: nativus producta in promptu sunt.

Features
1. Arca e aluminio zinci scheda obducta, quae a CNC instrumento processit et cum valvis vel claviculis conglobatur, cum structura plene modulari.
2. Haec switchgear varias functiones habet ad praecavendas misoperationes, inter quas impedimenta onusta movenda prohibent, ne coitu et permutationibus vivariis inpediantur, et inadvertentia ingressum in cellulas vivas impediant.
3. Switchgear cum ZN85 vacui circuli ruptor egregiis et carro perficiendis instructus est, et busbarum pelagus iungitur sine translationis transitus necessitate.
4.This switchgear est provectus, stabilis effectus, rationabilis structura, facilis to-
utere, salva et certa potentia armorum distribution

Technical data

Switchgear parametri

Nec. Item Unitas Precium
1 Rated voltage kV 40.5
2 Ratum current A 630/1250/1600/2000/2500
3 Rated frequency Hz 50/60
4 Potentia frequency voltage in 1 min sustinere Phase, Earthed kV 95
lsolating Fractura kV 110
5 Fulmen impetus sustinere voltage (Peak) Phase, Earthed kV 185
lsolating Fractura kV 215
6 Rated current of pelagus busbar A 630/1250/1600/2000/2500
7 Ratum vena rami busbar A 630/1250/1600/2000/2500
8 Rated brevis-circuitu fractionis current kA 20/25/31.5
9 Rated breve tempus sustinere current kA 20/25/31.5
10 Rated apicem sustinere current kA 50/63/80
11 Ratum ambitum brevem currentem faciens kA 50/63/80
12 Frequentia sustinere intentione in 1min aux imperium loop V 2000
13 arcus lnterni durationis test(0.5s) kA 31.5
14 Gradus praesidium IP IP4X(IP2X cum ianua aperitur)
15 Rated voltage of aux control loop V AC vel DC 110/220

ZN85-40.5 parametri

Nec. Item Unitas Data
1 Rated voltage kV 40.5
2 Nulla campester rated fulgur impetus sustinere voltage (fluctus plenus) kV 185
I min potentiae frequency sustinere voltage kV 95
3 Rated frequency Hz 50
4 Ratum current kA 630 630/1250 1250/1600/2000/2500
5 Rated brevis -circuit fractionis current kA 20 25 31.5
6 Ratum brevis -circuit faciens current kA 50 63 80
7 Ratum sustinet vena (apicem) kA 50 63 80
8 Rated breve tempus sustinere current kA 20 25 31.5
9 Certo tempore fractionis s ≤0.07
10 faciens tempus Electro-magnetica machina s Electro-magnetica mechanism≤0.2
Veris mechanism s Mechanismum vere ≤0.10
11 Operatio ordine rated / Apertum-0.3s-prope apertum 180s-prope apertum
12 Mechanica vita temporibus 10000

Features

2

Una linea tabula

3
4
5
Epistulam tuam hic scribe et mitte nobis